Compare cooling and heating performance

Use coefficients of performance and temperature lift without confusing heat movement with energy creation.

Learning outcome: Calculate cooling and heating COP, derive reversible bounds and distinguish per-cycle ratios from capacity and seasonal performance.

Starting recap

Heat delivered Qh equals heat removed Qc plus work input Win. These quantities are positive magnitudes for the proposed cycle.

All lessons are open directly. Your saved experiments remain when you leave and return.

Try

A heat pump delivers more heat than the work supplied to it. Does a COP greater than 1 violate energy conservation?

Open the experiment

Predict

For the default proposal, predict whether heating COP exceeds cooling COP, and by how much. Then predict how reducing the temperature lift changes the reversible bound.

Experiment

At 240 K/300 J, calculate both COPs from the energy ledger. Keep work at 300 J and compare cold temperatures 200 K and 280 K: the proposed energy split stays fixed but its entropy status changes. Explain the difference between a proposed COP, its bound and measured device performance.

Account for cooling, work input and delivered heat

Worked teaching model · synthetic values · A proposed cyclic device removes 1000 J per cycle from a fixed-temperature cold reservoir and delivers heat only to a 300 K reservoir. Work input is a nonnegative magnitude from ideal mechanical storage. No mass exchange, auxiliary inputs, other heat contacts or state accumulation. Energy balance is imposed; an entropy check may reject the proposal. Coefficients of performance are undefined at zero work input. No refrigerant, compressor, electrical conversion efficiency, temperature evolution, operating rate or real-device rating is modeled.

Reset keeps your prediction, captures and practice history.

Passes entropy screen · The proposed transfers pass this necessary entropy check; this is not a performance rating.

Proposed transfers · first two inputs sum to the third output040080012001600From cold reservoirWork into deviceTo warm reservoirEnergy (J) · dashed marker: minimum work input
Proposed performance and reversible bounds
QuantityProposalBound for these reservoirs
Work input per cycle300 JAt least 250.000 J
Cooling COP = Qc / Win3.333At most 4.000
Heating COP = Qh / Win4.333At most 5.000
Entropy changes for the proposed cycle
PartHeat into part (J)Temperature (K)Entropy change (J/K)
Cold reservoir−1000240-4.166667
Warm reservoir13003004.333333
Cyclic deviceNet −300Not specified along cycle0 (returns to initial state)
Combined with ideal work storageNo external heatNo single temperature0.166667

Cold-side removal 1000 J + work input 300 J = warm-side delivery 1300 J. For this same device and boundary, heating COP equals cooling COP plus 1. COP greater than 1 measures heat moved per unit work; it is not an energy-conversion fraction.

Passes entropy screen. Proposed cooling 1000 J + work input 300 J = delivered heat 1300 J per cycle.

Minimum reversible work 250.000 J; combined entropy change 0.166667 J/K. Passing this screen does not demonstrate a finite-power device.

Captures preserve recipes and replay their calculated results. They are synthetic model evidence, not physical measurements.

Understand

Choose what service you are counting

At the default proposal, the device removes 1000 J from the cold reservoir, receives 300 J of work and delivers 1300 J to the warm reservoir. A cooling user values the 1000 J removed. A heating user values the 1300 J delivered. The work input is the resource used in both comparisons.

The coefficient of performance, or COP, is the useful heat service divided by work input. For cooling, COPc = Qc/Win = 1000/300 ≈ 3.333. For heating, COPh = Qh/Win = 1300/300 ≈ 4.333. These ratios have no units and are not percentages of work converted into heat. The device transfers heat already present in the cold reservoir, in addition to receiving work.

For this same cycle and boundary, Qh = Qc + Win. Dividing by positive Win gives COPh = COPc + 1. Check that relation at several settings. It need not describe two unrelated appliances with different conditions or accounting boundaries. At zero work input the ratios are undefined, and the finite-transfer proposal in this lab is rejected.

Derive bounds for the two services

The second law gives Win ≥ Qc(Th−Tc)/Tc. Dividing the cooling service Qc by positive work yields the reversible bound:

COPc ≤ Tc/(Th−Tc).

Adding one gives COPh ≤ Th/(Th−Tc). Both use absolute temperatures with Th > Tc > 0. They describe a device exchanging heat only with these two reservoirs and receiving work, with no other changes. The reversible equality case follows from the same thermal reasoning as the Carnot-cycle reference.

At Tc = 240 K and Th = 300 K, cooling COP cannot exceed 4, and heating COP cannot exceed 5. The default 300 J proposal is below both limits and passes the entropy screen. At 250 J it reaches both limits. At 200 J it proposes cooling COP 5 and heating COP 6, exceeding the limits and failing the screen. A larger reported COP is not automatically a credible improvement.

Change the temperature lift

Keep work input at 300 J while changing the cold reservoir temperature. Heat removal stays 1000 J and warm-side delivery stays 1300 J, so the proposed COPs stay 3.333 and 4.333. However, the permissible limits change.

At 200 K, the temperature lift to 300 K is 100 K. Minimum work is 500 J; maximum cooling COP is 2 and heating COP is 3. The 300 J proposal is rejected, with total entropy change 1300/300−1000/200 = −0.666667 J/K.

At 280 K, the lift is only 20 K. Minimum work is about 71.429 J, cooling COP is bounded by 14 and heating COP by 15. The same 300 J proposal passes the entropy screen, with combined change about +0.761905 J/K. A smaller temperature lift relaxes this ideal work requirement; it does not guarantee that a particular real machine achieves the bound.

Separate a ratio from capacity

The lab uses energy per cycle and specifies no cycle rate. COP alone does not tell you how fast a room warms or a freezer removes heat. If a separate assumption supplied two cycles per second for the default proposal, the cooling rate would be 2000 J/s = 2 kW, the work-input rate 0.6 kW, and the heating rate 2.6 kW. These rates are conditional arithmetic, not a performance prediction from this model.

A measured system-level COP would need a stated operating period, temperatures and boundary, including the relevant compressor, fan, pump and control inputs. Seasonal performance needs evidence across changing conditions; one ideal cycle is insufficient. The work input here is mechanical, so no electricity use or cost is inferred without conversion and operating information.

Transfer using a heating specification

A heat pump delivers 4500 J per cycle to the warm side while receiving 1500 J of work. Calculate the heat removed from the cold side, both COPs, and explain why the heating ratio does not violate energy conservation. Would the energy figures alone prove it can operate between any two reservoir temperatures?

Check the heat-pump transfer

Cold-side removal is 4500−1500 = 3000 J. Cooling COP is 3000/1500 = 2; heating COP is 4500/1500 = 3. The extra delivered heat comes from the cold side, so energy balances. Feasibility still depends on reservoir temperatures and the entropy balance; energy figures alone do not establish it.

Apply

For the same cyclic device with Qc = 1200 J, Win = 400 J and no other energy transfers, cooling COP and heating COP are:

Public practice checks a specific claim. It does not establish independent mastery.

Explain the source of the extra delivered heat, define the selected useful output and system boundary, and state what rate or real-device evidence is missing.

Continue

Completion requires a saved prediction, at least one capture and a reflection. Presence checks do not grade your reasoning.

Skipping retains experiments and awards no mastery.

Save a science backup or import one

Science work is stored locally in this browser, separately from mathematics and AI. It does not sync automatically. Use this science-only backup; this checkout's older all-subject export does not include science.

A legacy file is available only when the complete snapshot fits the 36 MB limit. For larger snapshots, prepare a complete file set below; never discard notebooks to make a smaller file.

Matching imported notebook drafts replace their current drafts. Omitted lessons and known first attempts remain. Export your current work first if you want to retain both drafts.

Complete file sets and course backups

A file set can hold more work than one science file. Keep its manifest and every part together. Each file is limited to 36 MB. This format needs this version of LearnAI or a compatible newer version; older versions can use only the legacy single-file backup above.